@ -691,6 +691,7 @@ Harmonic content of the DDS signals from 4410 DDS Urukul is tabulated below\foot
|
||||||
|
|
||||||
\end{multicols}
|
\end{multicols}
|
||||||
|
|
||||||
|
\newpage
|
||||||
\section{Urukul Mode Configurations}
|
\section{Urukul Mode Configurations}
|
||||||
Mode of operation is specified by a DIP switch.
|
Mode of operation is specified by a DIP switch.
|
||||||
The DIP switch can be found at the top right corner of the card.
|
The DIP switch can be found at the top right corner of the card.
|
||||||
|
@ -720,6 +721,28 @@ The following table summarizes the required setting for each mode.
|
||||||
|
|
||||||
\end{multicols}
|
\end{multicols}
|
||||||
|
|
||||||
|
Note for Default mode: Switching on DIP Switch 3 enables the options that distribute the synchronization signals externally.
|
||||||
|
However, ARTIQ \& the core device (Kasli/Kasli-SoC) do not interact with these signals.
|
||||||
|
|
||||||
|
\section{Urukul 1-EEM/2-EEM Modes}
|
||||||
|
4410/4412 DDS Urukul can operate with either 1 or 2 EEM connections.
|
||||||
|
It is in 1-EEM mode when only EEM0 is connected, 2-EEM mode when both EEM0 \& EEM1 are connected.
|
||||||
|
2-EEM mode provides these additional features in comparison to 1-EEM mode.
|
||||||
|
\begin{itemize}
|
||||||
|
\item 1 ns temporal resolution RF switches \\
|
||||||
|
Without EEM1, the only way to access the switches is through the CPLD using SPI. \\
|
||||||
|
With EEM1, RF switches can be controlled as a TTL output through the LVDS transceiver.
|
||||||
|
1 ns temporal resolution is achieved using the ARTIQ RTIO system.
|
||||||
|
|
||||||
|
\item SU-Servo (4410 DDS Urukul feature) \\
|
||||||
|
SU-Servo requires both EEM0 \& EEM1 to control multiple DDS channels simultaneously using the QSPI interface.
|
||||||
|
|
||||||
|
\item Distribute synchronization signals from Urukul (4410 DDS Urukul feature) \\
|
||||||
|
Synchronization signals can only be distributed externally through EEM1.
|
||||||
|
ARTIQ \& the core device (Kasli/Kasli-SoC) will never interact with these signals.
|
||||||
|
|
||||||
|
\end{itemize}
|
||||||
|
|
||||||
\newpage
|
\newpage
|
||||||
|
|
||||||
\section{Example ARTIQ code}
|
\section{Example ARTIQ code}
|
||||||
|
|
Loading…