readme: update docs on max_i_neg command and heat flow directions
This commit is contained in:
parent
8eb3cc4307
commit
a1a8efd51a
22
README.md
22
README.md
|
@ -101,7 +101,7 @@ formatted as line-delimited JSON.
|
|||
| `report mode <off/on>` | Set report mode |
|
||||
| `pwm` | Show current PWM settings |
|
||||
| `pwm <0/1> max_i_pos <amp>` | Set PWM duty cycle for **max_i_pos** to *ampere* |
|
||||
| `pwm <0/1> max_i_neg <amp>` | Set PWM duty cycle for **max_i_neg** to *ampere* |
|
||||
| `pwm <0/1> max_i_neg <amp>` | Set PWM duty cycle for **max_i_neg** to *- ampere* |
|
||||
| `pwm <0/1> max_v <volts>` | Set PWM duty cycle for **max_v** to *volt* |
|
||||
| `pwm <0/1> i_set <amp>` | Disengage PID, set **i_set** DAC to *ampere* |
|
||||
| `pwm <0/1> pid` | Set PWM to be controlled by PID |
|
||||
|
@ -176,9 +176,13 @@ postfilter rate can be tuned with the `postfilter` command.
|
|||
|
||||
## Thermo-Electric Cooling (TEC)
|
||||
|
||||
- Connect Peltier device 0 to TEC0- and TEC0+.
|
||||
- Connect Peliter device 1 to TEC1- and TEC1+.
|
||||
- The GND pin is for shielding not for sinking Peltier currents.
|
||||
- Connect TEC module device 0 to TEC0- and TEC0+.
|
||||
- Connect TEC module device 1 to TEC1- and TEC1+.
|
||||
- The GND pin is for shielding not for sinking TEC module currents.
|
||||
|
||||
When using a TEC module with the Thermostat, the Thermostat expects the thermal load (where the thermistor is located) to heat up with a positive software current set point, and cool down with a negative current set point.
|
||||
|
||||
Testing heat flow direction with a low set current is recommended before installation of the TEC module.
|
||||
|
||||
### Limits
|
||||
|
||||
|
@ -199,6 +203,16 @@ Example: set the maximum voltage of channel 0 to 1.5 V.
|
|||
pwm 0 max_v 1.5
|
||||
```
|
||||
|
||||
Example: set the maximum negative current of channel 0 to -3 A.
|
||||
```
|
||||
pwm 0 max_i_neg 3
|
||||
```
|
||||
|
||||
Example: set the maximum positive current of channel 1 to 3 A.
|
||||
```
|
||||
pwm 0 max_i_pos 3
|
||||
```
|
||||
|
||||
### Open-loop mode
|
||||
|
||||
To manually control TEC output current, omit the limit parameter of
|
||||
|
|
Loading…
Reference in New Issue