Add Urukul PLL lock timeout failure

Signed-off-by: Egor Savkin <es@m-labs.hk>
This commit is contained in:
Egor Savkin 2023-03-27 12:23:13 +08:00
parent 8648e60009
commit 716b368319
2 changed files with 12 additions and 2 deletions

View File

@ -19,7 +19,7 @@ Put the `ext_ref_frequency` field into the JSON description if the Kasli is goin
On peripherals you should choose `"clk_sel": 2` on connected devices.
## Setup
## Setup external clocker
For tests, you may need an external RF generator, depending on customer needs.
Here is example setup for SynthNV RF signal generator:

View File

@ -103,3 +103,13 @@ ValueError: Urukul proto_rev mismatch
```
Check the ports are connected respectively to the JSON description.
### PLL lock timeout
```pycon
ValueError: PLL lock timeout
```
This can happen due to lack/bad clock source connection. Check that clock source is connected respective to the customer needs,
and if it is connected to the [Clocker](clocker.md), check that clocker receives clock signal properly and `EXT`/`INT` pin
matches real clocker source.