1
0
Fork 0

Add MCX TTL instructions

Signed-off-by: Egor Savkin <es@m-labs.hk>
This commit is contained in:
Egor Savkin 2023-03-07 13:31:51 +08:00
parent 922d6aa2b5
commit 07daab76f2
7 changed files with 66 additions and 9 deletions

View File

@ -6,6 +6,7 @@
- [Sinara 4456 synthesizer Mirny / Sinara 4457 Almazny Mezzanine card](./hw/mirny_almazny.md)
- [SUServo (Sampler + Urukul)](./hw/suservo.md)
- [Sinara 2118 BNC-TTL / 2128 SMA-TTL](./hw/bnc_sma_ttl.md)
- [Sinara 2138 MCX-TTL](./hw/mcx_ttl.md)
- [Sinara 5432 DAC Zotino / Sinara 5632 DAC Fastino](./hw/zotino_fastino.md)
- [Sinara 5518 BNC-IDC / 5528 SMA-IDC adapter](./hw/bnc_sma_idc_adapter.md)
- [Sinara 4410/4412 DDS Urukul (AD9910/AD9912)](./hw/urukul.md)

View File

@ -55,6 +55,8 @@ nix build -L --impure --expr 'let fl = builtins.getFlake "git+file://<path to ar
# copy `results/boot.bin` to the SD card
# insert SD card to the Kasli-SoC and boot
artiq_coremgmt -D 192.168.1.56 config write -s ip 192.168.1.75
# update firmware
artiq_coremgmt config write -f boot result/boot.bin
# reboot via power supply
artiq_sinara_tester
```

View File

@ -4,7 +4,7 @@
## JSON
Put the `ext_ref_frequency` field into the JSON description if the Clocker is going to use an external frequency:
Put the `ext_ref_frequency` field into the JSON description if the Kasli is going to use an external frequency:
```json
{
@ -38,14 +38,16 @@ Here is example setup for SynthNV RF signal generator:
### Setup the Clocker
1. Connect MMCx cables according to the customer needs and boards specifications (see image below for reference)
2. Connect the Clocker to the Kasli via 30-pin ports
1. Switch `CLK SEL` pin to `EXT`/`INT` according to customer needs
2. Connect MMCx cables according to the customer needs and boards specifications (see image below for reference):
if the `INT` source is chosen, connect MMCx cable to `INT CLK`, otherwise connect external clocker to SMA `EXT CLK`
3. Connect the Clocker to the Kasli via 30-pin ports
![](../img/clocker_ref.jpg)
3. Connect the Clocker's SMA output to the Kasli's `CLK`/`CLK IN` SMA pin
4. After assembling the crates and flashing the firmware, start Kasli and write config as follows:
4. Connect the Clocker's SMA output to the Kasli's `CLK`/`CLK IN` SMA pin
5. After assembling the crates and flashing the firmware, start Kasli and write config as follows:
`artiq_coremgmt config write -s rtio_clock ext0_bypass`. Please refer to the [official manual](https://m-labs.hk/artiq/manual/installing.html#miscellaneous-configuration-of-the-core-device)
for the details and available options
5. Reboot either via `artiq_coremgmt reboot` or via power supply if the board's firmware doesn't have such command
6. Reboot either via `artiq_coremgmt reboot` or via power supply if the board's firmware doesn't have such command
## Testing

41
src/hw/mcx_ttl.md Normal file
View File

@ -0,0 +1,41 @@
# Sinara 2238 MCX TTL card
[Wiki](https://github.com/sinara-hw/DIO_MCX/wiki)
[Datasheet](https://m-labs.hk/docs/sinara-datasheets/2238.pdf)
# JSON
```json
[
{
"type": "dio",
"board": "DIO_MCX",
"ports": [0],
"edge_counter": true, // optional
"bank_direction_low": "input",
"bank_direction_high": "output"
},
{
"type": "dio",
"board": "DIO_MCX",
"ports": [1],
"bank_direction_low": "output",
"bank_direction_high": "output"
}
]
```
Since MCX TTL has twice as much as BNC/SMA cards, it is treated as two cards - there are 2 ports to be connected
and 2 entries in the JSON.
## Setup
Switch the direction switches (shown on the picture below) according to customer requests.
Remember, that you can only switch directions in groups of four.
![](../img/ttl_mcx.jpg)
## Test
Refer to the [BNC/SMA TTL instructions](bnc_sma_ttl.md) for testing, but chose appropriate connector,
and respect increased number of channels.

View File

@ -10,13 +10,15 @@
"type": "urukul",
"dds": "<variant>", // ad9910/ad9912
"ports": [<port num>, <port num>],
"clk_sel": <clock num>
"clk_sel": <clock num>,
"refclk": <freq>, // for external clock signal
"pll_en": <0 or 1, default 1> // PLL bypass, to allow higher external clocker frequencies (1e9 for example)
}
```
## Setup
Check if [SUServo](./suservo.md) is enabled/disabled on customer needs.
Check if [SUServo](./suservo.md) is enabled/disabled respective to customer needs. Connect to the clocker source.
## Testing
@ -84,3 +86,12 @@ ValueError: no valid window/delay
Check with the customer to see if synchronization is necessary, and disable it if it is not.
In any case, simply restart the test.
### Noise instead of signal
It may be due to misconfiguration of SUServo. Check that both firmware and pins enable/disable the SUServo mode.
### Improper frequency
This can happen due to lack/bad clock source connection. Check that clock source is connected respective to the customer needs,
and if it is connected to the [Clocker](clocker.md), check that clocker receives clock signal properly.

Binary file not shown.