forked from M-Labs/thermostat
parent
dc41473493
commit
93ea46d512
12
README.md
12
README.md
|
@ -157,6 +157,18 @@ Set the Beta parameter:
|
||||||
s-h 0 b 3800
|
s-h 0 b 3800
|
||||||
```
|
```
|
||||||
|
|
||||||
|
### 50 Hz filtering
|
||||||
|
|
||||||
|
The AD7172-2 ADC on the SENS inputs supports simultaneous rejection of
|
||||||
|
50 Hz ± 1 Hz and 60 Hz ± 1 Hz (dB). Affecting sampling rate, the
|
||||||
|
postfilter rate can be tuned with the `postfilter` command.
|
||||||
|
|
||||||
|
| Postfilter rate | Rejection | Effective sampling rate |
|
||||||
|
| --- | :---: | --- |
|
||||||
|
| 16.67 Hz | 92 dB | 8.4 Hz |
|
||||||
|
| 20 Hz | 86 dB | 9.1 Hz |
|
||||||
|
| 21.25 Hz | 62 dB | 10 Hz |
|
||||||
|
| 27 Hz | 47 dB | 10.41 Hz |
|
||||||
|
|
||||||
## Thermo-Electric Cooling (TEC)
|
## Thermo-Electric Cooling (TEC)
|
||||||
|
|
||||||
|
|
Loading…
Reference in New Issue